PQ Edge Cost-effevtive, scalable power monitoring and analysis for mission-critical equipment
Safeguard Mission-Critical Equipment ,
Against Operational Risk and Downtime
In critical sectors like data centers and medical imaging, the reliability of high-tech electronics is paramount — and it hinges on power quality. Inferior or unreliable power, characterized by transients, harmonics and distortions, can lead to big problems like outages, flicker, equipment damage, inaccurate readings and more.
Enter the PQ Edge Power Analyzer
Designed to alert you to these risks the moment they happen, the PQ Edge™
unlocks visibility into your power quality issues before they become a problem.
When assessing your electric power, the PQ Edge helps ensure poor power quality doesn’t negatively impact your equipment.
PQ Edge™ |
|
Technical specifications |
|
Dimensions (L x W x H) |
5.52 in X 3.78 in X 2.38 in (14.02 cm X 9.60 cm X 6.04 cm), 1.8 in (3.5cm ) DIN rail mountable |
Weight |
8.4 oz (238g) |
Operating Environment |
Temperature: -40 to +158°F (-40 to +70°C); humidity: 5-95% RH (inside use); altitude: <2000m above sea level |
Power Supply |
AC: 24 Vac ±10% at 50/60 Hz, 1.5A max; DC: ±24 to 48 Vdc ±10% (polarity independent), 1A max. |
Internal Memory |
32 GB |
Data Backup |
USB 2.0 thumb drive |
Clock Synchronization |
SNTP, NTP |
Output File Types |
Text, GIF, CSV, and IEEE 1159-3 PQDIF |
Communication Ports |
Ethernet RJ45 10/100 (optional external wireless or cell modem) |
Communication Protocols |
Modbus/TCP, DNP 3.0, SNMP with traps, BACnet, FTP or HTTP (secure FTPS and HTTPS, and email) |
Voltage |
|
Sampling Rate |
512 samples per cycle at 50 Hz/60 Hz (applies to voltage and current channels) |
Inputs |
4 + reference to earth (L1, L2, L3, N, E) |
Voltage Range |
0 to 750 Vac (L-N), 0 to 1300 Vac (l-L), impedance: 4.8MΩ |
Voltage Magnitude* |
L-L, L-N, L-E, and N-E. RMS over 1/2 cycle (Urms 1/2) |
Frequency* |
50 Hz, 60 Hz, 400 Hz |
Unbalance (negative & zero sequence)* |
IEC, GB, and ANSI methods |
Flicker (Pinst, Pst, & Plt)* |
IEC 61000-4-15 |
Voltage Harmonic & Interharmonic* |
Volt, or %H1, IEC 61000-4-7 Class 1, order up to 50th |
Total Harmonic Distortion (THD) |
%, IEC 61000-4-7 |
Conducted Emissions (2-9 kHz)* |
Volts for L1-E, L2-E, L3-E: resolution 200 Hz bins, range 0 to 60 Vpk |
Current |
|
Inputs |
4 inputs (l1 to l4), differential; nominal input: 0.333 Vrms; impedance: 33.3 kΩ |
Current Magnitude* |
RMS refreshed 1/2 cycle (lrms 1/2) |
Peak Current |
RMS over 1 sec, 1 min, or user defined (3 min to 1 hr) |
Unbalance (negative & zero sequence)* |
IEC, GB, and ANSI methods |
Current Harmonics & Interharmonics* |
Amp, order up to 50th |
Total Demand Distortion (TDD) |
Amp, IEC 61000-4-7 |
Total Harmonic Demand Distortion (THDI) |
%, IEC 61000-4-7 |
Power |
|
Channels |
4 calculated channels. l1 to l4, calculated either L1-N, L2-N, or L3-N voltages |
Total Power |
One 3-phase load |
Peak Power |
Intervals: 1 sec, 1 min or user defined (up to one hour) |
Reactive Power |
VAR (per-phase and total) |
Apparent Power |
VA (per-phase, peak, and total) |
Power Factor |
TPF or DPF method (per-phase and total) |
Energy |
|
Channels |
4 channels. l1 to 4 calculated with one three phase channel or four single phase channels |
Energy (Import, Export, & Net) |
kWH (per-phase and total); accuracy certified ANSI C12.20 Class 0.5 and IEC 62053-22 Class 0.5 |
Reactive Energy (Import, Export, & Net) |
kVARh (per-phase and total) |
Apparent Energy |
kVAh (per-phase and total) |
Environment sensors |
|
Inputs |
1 ENV2 probe input (USB port, shared with USB drive) |
Temperature |
-4 to 176°F (-20 to 80°C) |
Humidity |
0 to 100% RH |
Barometric Pressure |
Resolution better than 0.001 hPa |
Acceleration (x, y, & z) |
(x, y, and z) ±2, ±4, or ±8 gravity ranges, trigger on shock/vibration, seismic or tilt |