AllThat Power

PQ Edge

PQ Edge

PQ Edge Cost-effevtive, scalable power monitoring and analysis for mission-critical equipment


JAESHININFO:
B106-ho, SK V1 Tower, Guenjeongyeok 2nd, 136 LS-ro, Dongan-gu, Anyang-si, Phone: 031-388-7874, E-mail : support@jsdata.co.kr
  • PQ Edge Overview
  • PQube3 Comparison Table
  • Specifications
  • PQ Edge+QubeScan
  • Installation Case
  • catalog
  • ITIC Application
  • video

 Safeguard Mission-Critical Equipment , 
Against Operational Risk and Downtime

In critical sectors like data centers and medical imaging, the reliability of high-tech electronics is paramount — and it hinges on power quality. Inferior or unreliable power, characterized by transients, harmonics and distortions, can lead to big problems like outages, flicker, equipment damage, inaccurate readings and more.

Enter the PQ Edge Power Analyzer

Designed to alert you to these risks the moment they happen, the PQ Edge™

unlocks  visibility  into  your power  quality issues before they become a problem.

When assessing your electric power, the PQ Edge helps ensure poor power quality doesn’t negatively impact your equipment.

PQ Edge™

Technical specifications

Dimensions (L x W x H)

5.52 in X 3.78 in X 2.38 in (14.02 cm X 9.60 cm X 6.04  cm),  1.8 in (3.5cm ) DIN rail mountable

Weight

8.4 oz (238g)

Operating Environment

Temperature: -40 to +158°F (-40 to +70°C); humidity: 5-95% RH (inside use); altitude: <2000m above sea level

Power Supply

AC: 24 Vac ±10% at 50/60 Hz, 1.5A max; DC: ±24 to 48 Vdc ±10% (polarity independent), 1A max.

Internal Memory

32 GB

Data Backup

USB 2.0 thumb drive

Clock Synchronization

SNTP, NTP

Output File Types

Text,  GIF, CSV, and  IEEE 1159-3 PQDIF

Communication Ports

Ethernet RJ45 10/100 (optional  external wireless or cell modem)

Communication Protocols

Modbus/TCP, DNP 3.0, SNMP with traps, BACnet, FTP or HTTP (secure FTPS and  HTTPS,  and  email)

Voltage

Sampling Rate

512 samples per cycle at 50 Hz/60 Hz (applies to voltage and current channels)

Inputs

4 + reference  to earth (L1, L2, L3, N, E)

Voltage Range

0 to 750 Vac (L-N), 0 to 1300 Vac (l-L), impedance:  4.8MΩ

Voltage Magnitude*

L-L, L-N, L-E, and N-E. RMS over  1/2 cycle (Urms 1/2)

Frequency*

50 Hz, 60 Hz, 400 Hz

Unbalance (negative & zero sequence)*

IEC, GB, and ANSI methods

Flicker (Pinst, Pst, & Plt)*

IEC 61000-4-15

Voltage Harmonic & Interharmonic*

Volt, or %H1, IEC 61000-4-7 Class 1, order up to 50th

Total Harmonic Distortion (THD)

%, IEC 61000-4-7

Conducted Emissions (2-9 kHz)*

Volts for L1-E, L2-E, L3-E: resolution 200 Hz bins, range 0 to 60 Vpk

Current

Inputs

4 inputs (l1 to l4), differential; nominal input: 0.333 Vrms; impedance: 33.3 kΩ

Current Magnitude*

RMS refreshed 1/2 cycle (lrms 1/2)

Peak Current

RMS over  1 sec, 1 min, or user defined  (3 min to 1 hr)

Unbalance (negative & zero sequence)*

IEC, GB, and ANSI methods

Current Harmonics & Interharmonics*

Amp, order up to 50th

Total Demand Distortion (TDD)

Amp,  IEC 61000-4-7

Total Harmonic Demand Distortion (THDI)

%, IEC 61000-4-7

Power

Channels

4 calculated channels. l1 to l4, calculated either L1-N, L2-N, or L3-N voltages

Total Power

One 3-phase load

Peak Power

Intervals: 1 sec, 1 min or user defined (up to one hour)

Reactive Power

VAR (per-phase and total)

Apparent Power

VA (per-phase, peak, and total)

Power Factor

TPF or DPF method (per-phase and total)

Energy

Channels

4 channels. l1 to 4 calculated with one three phase channel or four single phase channels

Energy (Import, Export, & Net)

kWH (per-phase and total); accuracy certified ANSI C12.20 Class 0.5 and IEC 62053-22 Class 0.5

Reactive Energy (Import, Export, & Net)

kVARh (per-phase  and total)

Apparent Energy

kVAh (per-phase and total)

Environment sensors

Inputs

1 ENV2 probe  input  (USB port, shared with USB drive)

Temperature

-4 to 176°F (-20 to 80°C)

Humidity

0 to 100% RH

Barometric Pressure

Resolution better than 0.001 hPa

Acceleration (x, y, & z)

(x, y, and z) ±2, ±4, or ±8 gravity ranges, trigger on shock/vibration, seismic or tilt

 

Google Map
© AllThat Power ^