Battery Monitoring System

Battery Monitoring System

Battery Monitoring System made in Korea


JSDATA Smart Cubic:
Jaeshininformation Co., Ltd

Compatible with the IEEE Std.1188-2005 maintenance recommendations on VRLA batteries,
▶ Measureeach Voltage, Temperature and Internal Resistance on VRLA and Ni-Cd batteries,
▶ Use a single CAN (Controller Area Network) BUS between Master and 100 Sensors,
▶ Measure all voltage& temp. in a 1 sec,  and all internal resistance on 400 cells in 30 sec.

 

E-mail : ceo@jsdata.co.kr 

Tel : +82-31-388-7874 

 

 

 

  

 

 

 

CellScan System Configuration

■ Features

The measuring speed of CAN (Controller Area Network) is very fast, and
During a discharge, a bad cell or inter-connection can be found by a measuring a voltage drop.
UPS with CAN communication can communicate directly with Sensor (without Master)

 

  

CellScan Master (Master)

CS-Sensor (Sensor)

System Capacity

Measuring Capacity

Max q’ty of sensor

100 Sensor per 1 Master

Type of sensor

LV sensor

4 cell measured by 2V/4V/6V/8V sensor

String current and voltage

Each 1 pcs

HV sensor

4 cell measured by 12V sensor

Comm. port

CAN bus (2) for Ring, Ethernet (1), RS-232 (1)

Comm. port

2 line of CAN BUS, which is the high reliable.

Ambient temp.

1 pcs

Temp. sensor

4 pcs

Measuring Speed

Measuring Speed

String voltage

0.1 sec

To measure each voltage and temperature on 400 cells

1 sec

 

 

To measure an internal resistance on 400 cells

30 sec

Range & Accuracy

Range & Accuracy

String voltage

~ 1,000VDC / ±0.5% of full scale

 

Cell voltage

~   9.0V / ±0.1% of ±10mV ( 2V)

String current

~ 1,000ADC / ±1.0% of full scale

~ 17.0V / ±0.1% of ±20mV (12V)

String ripple current

~ 1,000Ap-p / ±5.0% of full scale

Cell temperature

-20 ~ +80℃ / ±1℃

Ambient temp.

- 20 ~ 80℃ / ±1℃

Cell internal resistance

0.1mΩ (4,000Ah) ~ 100.0mΩ  / ±2.0%

Resolution

Resolution

String voltage

0.1V      /    0.1A String current

Cell voltage

1mV

String ripple current

0.1Ap-p  /    0.1℃ Ambient temperature

Cell temperature

0.1 ℃

 

Cell internal resistance

0.001mΩ

Dimensions & Environment

Dimensions & Environment

Dimensions

200 × 150 × 34㎜ (45㎜)

Dimensions

128 × 61 × 35㎜

Environment

Temperature: 0~50 ℃ / under Humidity: 80%RH

Environment

Temperature: 0~50 ℃ / under Humidity: 80%RH

Feature

 

?When the digit of CAN ID flash, CAN bus is abnormal.

?When CAN ID and its communication are abnormal, it will be displayed.

?The measuring period on cell voltage and temperature is (1 sec), and to measure an internal resistance on all cells is (30 sec) in maximum, which are changeable.

Feature

?When the digit of CAN ID flash, CAN bus is abnormal.

?When CAN ID and its communication are abnormal, it will be displayed.

?The measuring period on cell voltage and temperature is (1 sec), and to measure an internal resistance on all cells is (30 sec) in maximum, which are changeable.

Installation Pictures

 

[S 종합 기술원]

[카길 애그퓨리나]

[카톨릭 IDC 센터]

[한국전력]

[S 정밀화학]

[L 보험 IDC 센터]

[S 그룹 사옥]

[인천복합화력발전소]

[S, K 통신사]

[3세대 센서 : Sentinel 3]

proposal download

■ CellScan Software



▶ To monitor the measured data by CellScan analysis program in a real time.
▶ To show all statistical data on all strings of batteries measured by CellScan.
▶ To show all alarm list in a real time and to record all history to operate.  
▶ To show each Voltage, Temperature and Internal-Resistance measured.
▶ To show a charging and discharging current and ripple current (waveform & FFT analysis).
▶ To show save a all measure data on a discharging and history information.
▶ To show the function of a discharging re-play.
▶ To supply e-mail and SMS service (option)